Product Category

Hover over picture to Zoom
Click to enlarge

SLP2565

SLP2565--PRESSURE SWITCH

High precision controls at economical prices. Encapsulated, non-adjustable, single pole - single throw, direct mount switches for use with HFC, HCFC, and CFC refrigerants.

Features/Benefits

  • ¼" SAE 45° female flare fitting with valve core depressor
  • Automatic Reset
  • Life at rated load: 100,000 cycles
  • Low pressure switch opens on pressure fall
  • Rated Voltage 24/120/240 VAC @ 50/60 Hz
  • Small size and light weight for direct mounting
  • Snap acting stainless steel hermetically sealed sensor
  • Wire is 18 AWG, 18" long
  • WARNING: Prop 65 info
Locate a Distributor Near You
Maximum FLA: 5.8 Amps @ 120VAC
Maximum FLA: 2.9 Amps @ 240VAC
Maximum LRA: 34.8 Amps @ 120VAC
Maximum LRA: 17.4 Amps @ 240VAC
Maximum Temperature: -31°F to 149°F (-35°C to 65°C)
Maximum Operating Pressure: 700 PSI
Burst Pressure: 2800 PSI
Close PSI: 65 PSI
Open PSI: 25 PSI
Tolerance: +/- 5 PSI
DC Voltage: 6Vdc/12Vdc/36Vdc
Agency Approvals: UL® Recognized, CE®
Heat pump systems
Air conditioning systems
Refrigeration Systems
SDS Product Sheets Cross Reference Information
no entry SLP2565_prd_001.pdf
no entry

Manuals Application Sheets Software
no entry no entry no entry

Replacement Part:33336
Part Description:
Manufacturer :Mars®

Replacement Part:43347
Part Description:
Manufacturer :Mars®

Replacement Part:3101002
Part Description:
Manufacturer :Robertshaw®

No Accessories Available

Do these carry any certifications/approvals?: Yes, they are UL® Recognized, and CE® Certified.
What is the difference between the part numbers? : It is the PSI rating the switches operate.
Do we carry anything for use with DC voltage?: No, just AC at this time.
Do we offer any custom made to our specs swithces? : No, we do not.
Can these switches be used in a 460V application?: No, the maximum voltage is 240VAC.