SLP4080
SLP4080--PRESSURE SWITCH
High precision controls at economical prices. Encapsulated, non-adjustable, single pole - single throw, direct mount switches for use with HFC, HCFC, and CFC refrigerants.
Features/Benefits
- ¼" SAE 45° female flare fitting with valve core depressor
- Automatic Reset
- Life at rated load: 100,000 cycles
- Low pressure switch opens on pressure fall
- Rated Voltage 24/120/240 VAC @ 50/60 Hz
- Small size and light weight for direct mounting
- Snap acting stainless steel hermetically sealed sensor
- Wire is 18 AWG, 18" long
- WARNING: Prop 65 info
Maximum FLA: | 5.8 Amps @ 120VAC |
Maximum FLA: | 2.9 Amps @ 240VAC |
Maximum LRA: | 34.8 Amps @ 120VAC |
Maximum LRA: | 17.4 Amps @ 240VAC |
Maximum Temperature: | -31°F to 149°F (-35°C to 65°C) |
Maximum Operating Pressure: | 700 PSI |
Burst Pressure: | 2800 PSI |
Close PSI: | 80 PSI |
Open PSI: | 40 PSI |
Tolerance: | +/- 5 PSI |
DC Voltage: | 6Vdc/12Vdc/36Vdc |
Agency Approvals: | UL® Recognized, CE® |
Heat pump systems |
Air conditioning systems |
Refrigeration Systems |
SDS | Product Sheets | Cross Reference Information |
no entry | SLP4080_prd_001.pdf |
no entry |
Manuals | Application Sheets | Software |
no entry | no entry | no entry |
Replacement Part:33364
Part Description:
Manufacturer :Mars®
Replacement Part:43350
Part Description:
Manufacturer :Mars®
Replacement Part:MPL7014
Part Description:
Manufacturer :Ranco®
Replacement Part:3101005
Part Description:
Manufacturer :Robertshaw®
Replacement Part:3100052
Part Description:
Manufacturer :Robertshaw®
No Accessories Available
Do these carry any certifications/approvals?: | Yes, they are UL® Recognized, and CE® Certified. |
What is the difference between the part numbers? : | It is the PSI rating the switches operate. |
Do we carry anything for use with DC voltage?: | No, just AC at this time. |
Do we offer any custom made to our specs swithces? : | No, we do not. |
Can these switches be used in a 460V application?: | No, the maximum voltage is 240VAC. |